- Tabletop stand
- Magnetic housing for magnetic mounting
- 4-point strap for effortless, hands-free use
- Backlit display for comfortable reading even in low light
- Terminal block with clear markings (L, N, PE, H, S, E, +, COM connections) to prevent incorrect connections
- Remote control probe for remote testing
- Tripod cable for direct measurements on 2P+E sockets.
The controller performs voltage, continuity, resistance, insulation, loop, and current measurements with an external clamp. The CA 6133 also performs phase rotation. AC and A residual current devices (RCDs) can be tested in ramp or pulse mode.
The CA 6133 provides an immediate visual indication of the test result (good/bad). Saving time, the CA 6133 allows you to initiate automatic test sequences and save the results. For example, a sequence like "AUTO LOOP-DDR-MΩ" can be saved. It allows for quick on-site preparation of a control campaign consisting of up to 6 to 8 successive tests.
A dedicated Android app, "IT Report," for electrical installation control allows you to download test results and generate and view the measurement report via Bluetooth.
Main technical characteristics:
- Voltage measurement: 550 VAC/800 VDC
- Continuity at 200 mA,
- Resistance from 1 to 99.99 kΩ
- Insulation: test voltage 250 V, 500 V, 1,000 V
- Loop Zs (Z L-PE) without triggering: from 1 to 2,000 Ω, Ik calculation
- High current loop Zs (Z L-PE) with triggering and Zi (Z LN or Z LL), from 0.1 to 400 Ω, Ik calculation
- AC and A type DDR: 30 mA, 100 mA, 300 mA, 500 mA, 650 mA
- Pulse mode DDR: trigger time
- Ramp mode DDR (30 mA): trigger current
- Phase rotation: from 45 to 550 V; 45 to 65 Hz
- Frequency measurement: 30 Hz to 999.9 Hz
- Insulation: additional test voltage of 1,000 V
- 3P ground (spike): up to 2,000 Ω
- Automatic DDR test sequence: no trip – pulse – ramp
- Automatic test sequence: Loop-DDR-MΩ
- Memory: 30 centers of 99 tests with the MEM key or optional remote control probe
- Powered by rechargeable batteries with integrated charger
- Recharging possible via mains power, USB plug or cigarette lighter
- Bluetooth communication
- Automatic recognition of the optional MN73A external clamp
Advantages
- Grounding measurement by probe and loop method
- Continuity measurement at 0.2 A
- Insulation testing
- DDR test: current and trigger time
- Automatic test sequences
- Test memory
- ANDROID application for generating reports
- Powered by rechargeable batteries via mains electricity, USB plug or cigarette lighter socket