D4i luminaires are becoming an ideal platform for the Internet of Things (IoT), capable of gathering information from integrated D4i sensors and providing data for performance monitoring, asset management, predictive maintenance, and many other tasks related to managing various lighting systems. Communication and information exchange with an external network can be achieved through a D4i control device/node with wireless data transmission capabilities.
D4i is an extension of the DALI-2 certification program. Both D4i control devices and D4i LED drivers are required to meet a set of mandatory specifications related to power requirements and the storage/transmission capabilities of the information described above. This article will detail all these mandatory requirements for obtaining D4i certification and delve into the most relevant information that can be obtained through the use of D4i devices.

Figure 1. Detail of the DALI parts that include the D4i standard and its mandatory nature for D4i certification of LED drivers and control devices.
D4i LED Drivers
As shown in Figure 1, the mandatory components for LED drivers to achieve D4i certification are DALI parts 250, 251, 252, and 253.
There is also an optional component, DALI part 150. As we will detail later, this component refers to a 24V auxiliary output that LED drivers can integrate.
Figure 1 also shows that implementing all these DALI components is optional for achieving DALI-2 certification for LED drivers.
DALI parts 251, 252, and 253 enable LED drivers to provide a wide range of data for real-time performance monitoring, diagnostic reports, energy measurement, and other applications, which we will detail below.
This information is stored in the LED driver's DALI memory banks (also called DALI Memory Banks or MB) and is related to the LED module, the LED driver itself, and the luminaire. The bidirectional nature of the DALI protocol allows this information to be transmitted through the lighting control network.
• DALI Part 150 – AUX Power Supply (integrated)
This part specifies the minimum requirements for a 24VDC auxiliary power supply (AUX) that can be used to power a load, such as a presence sensor or communication node, if the power supplied by the DALI bus source is insufficient. Integrating it within the LED driver eliminates the need for an additional AC/DC converter, as well as the surge protector and EMI filter associated with this external device, thus enabling significant cost and space reductions during the manufacturing and design of the luminaire.
Some of the main requirements for the AUX power supply as defined by DALI Part 150 are:
- Nominal power: 3W
- Peak power: 6W (2.2ms)
- Nominal output voltage: 24V (+/-10%)
• DALI Part 250 – Integrated Bus Power Supply
This part specifies the characteristics of a DALI bus power supply integrated into a control gear (LED driver).
Some of the main requirements for the integrated DALI bus power supply covered by DALI Part 250 are:
- Guaranteed DALI current: 50mA (minimum)
- The DALI bus power supply must be switchable (it must be able to be turned on/off)
• DALI Part 251 – Luminaire Data
This part specifies an extension to memory bank 1 (MB1) to enable advanced asset management. The information it contains refers to luminaire data and is typically written by the luminaire manufacturer to the LED driver's memory during the manufacturing process.
The main information contained in the MB1 extension about the luminaire, as specified in DALI Part 251, is:
- Input power (W)
- Input voltage (V)
- Nominal intensity (lm)
- Light distribution type
- Year and week of manufacture
- GTIN, serial number, and model
- CCT (K)
- CRI
• DALI Part 252 – Energy Data
This part specifies the information related to energy reporting data accessible through the LED driver's memory banks. It includes the following memory banks: MB202 (mandatory), MB203 (optional), and MB204 (optional).
The main information contained in the MB202 is as follows:
- Active energy (Wh)
- Active power (W)
The main information contained in the MB203 is as follows:
- Apparent energy (VAh)
- Apparent power (VA)
The main information contained in the MB204 is as follows:
- Active energy of the load/LED module (Wh)
- Active power of the load/LED module (W)
• DALI Part 253 – Diagnostics Data
This part specifies information related to diagnostic and maintenance data. It includes the following mandatory memory banks: MB205 – Control gear diagnostics and maintenance, MB206 – Light source diagnostics and maintenance, and MB207 – Luminaire maintenance data.
The main information contained in the MB205 regarding the LED driver is as follows:
- Operating time (s)
- Number of switches
- Supply voltage (Vrms)
- Supply frequency (Hz)
- Power factor
- Driver fault indication (total, input voltage, overload, over-temperature…)
- Counter of total faults of each type
- Internal temperature (°C)
- Percentage of output current (%)
The main information contained in the MB206 regarding the LED module is as follows:
- Operating time (s)
- Number of switches
- LED module voltage (V)
- LED module current (A)
- LED module fault indication (total, short circuit, open circuit, over-temperature…)
- Counter of total faults of each type
- LED module temperature (°C)
The main information contained in the MB207 regarding the luminaire is as follows:
- Average luminaire lifetime (h)
- Reference internal driver temperature at 25°C ambient temperature (°C)
- Number supported ignition medium
D4i CONTROL DEVICES
The mandatory part that applies to control devices in order to obtain D4i certification is DALI part 351.
• DALI Part 351 – Luminaire-mounted control devices.
D4i control devices can be powered directly from the DALI bus, as well as via an auxiliary power supply (AUX). DALI Part 351 defines four different classes of control devices (types A, B, C, and D) and includes specific requirements regarding their power consumption. It also adds a mechanism for determining which control device takes priority when more than one is present in the DALI system.
Types A, B, C, and D cover all types of applications (indoor and outdoor) and include devices such as wireless lighting controllers (nodes), light sensors, and motion sensors. For more information, see article DALI-2. Control devices: types and configuration.
DALI IN-LUMINAIR APPLICATION
is particularly well-suited for what are known as intra-luminaire DALI applications. This refers to a DALI bus that connects LED drivers and control devices within an individual luminaire, enabling the creation of smart, IoT-ready luminaires.

Figure 2. Intraluminary DALI. Example of application in an outdoor luminaire with two nodes (communications + presence/luminosity sensor).
HOW CAN WE OBTAIN D4i INFORMATION?
In the previous figure (Fig. 2), we can see an in-luminaire DALI system that incorporates a D4i-certified Casambi communication node ( CAS-UNI-NEMA-5P-010DA-RL-LX* ). Through the Casambi application, we can quickly and in real time access all the information available in the memory banks of the D4i LED driver ( APD-040-C105-ARE* ), as shown on the left side of Figure 3. (*Products distributed by Electrónica OLFER ).
If our lighting system needs to store this information for later analysis or to create temporary graphical representations on a dashboard, we can use the Casambi API to collect this information and process it through our own lighting management platform (right side of Figure 3).

Figure 3. D4i data queried through the Casambi app (left) and exported for visual representation via API (right).
In conclusion, and as we have been highlighting throughout this article, by integrating D4i devices into luminaires we provide access to a variety of information that can be very useful for maintenance personnel and owners of lighting systems when managing, analyzing and maintaining their installations in a practical, fast and highly efficient way.