Not only can we create redundant 1+1 and N+1 applications without the need for any external components, but they also include a hot-swap connection system for quick replacement. This simplifies connection while reducing the number of components, potential connection and wiring errors, and replacement time in case of failure.

The CP DIMENSION series features very high efficiency, active PFC, and active inrush current limiting. This prevents excessive input current draw that could trip circuit breakers. We no longer need to calculate how many power supplies we can connect per circuit breaker or use more expensive C or D slow-curve equipment. Simply considering the nominal input current draw tells us how many power supplies we can connect to that line. It complies with ATEX and IECEx certifications for hazardous areas.

This R version incorporates a MOSFET decoupling diode that minimizes losses in the power supply's output stage. No redundant modules are required. This model saves space and connection time, reduces energy losses, and simplifies high-reliability applications. It features a permanent parallel load sharing system. The CP10.241-R2 is suitable for applications where units need to be replaced while in operation, as it has plug-in connectors for hot-swapping.

It has 20% extra power that can be used permanently as long as we do not exceed 45ºC ambient temperature.

They offer up to 3 times the nominal output current for a minimum of 12ms in order to trigger any protection we have at the output, in case of feeding several branches and thus isolate the branch that has a short circuit.

Its high resistance to transients, low electromagnetic emissions and a large number of approvals facilitate its use in any application.

PULS power supplies feature excellent thermal design and are sized for continuous operation at maximum power. Their MTBF typically reaches several million hours, with an expected lifespan of over 7 years at full load. For any demanding application where you want a hassle-free installation, PULS is the ideal solution.

Features:
Wide input range from 85 to 264VAC (300VAC for 5 seconds).
DC input range: 88-180VDC (88-360VDC for model CP10.242.R2).
Output: 24VDC, 10 Amps, 240W. 12 Amps continuous current allowed at temperatures below 45°C.
48mm wide.
Integrated MOSFET for 1+1 and n+1 redundancy.
Overload protection with Hiccup PLUS system.
MOSFET (transistor) technology as a decoupling device for minimal power loss.
Active power factor correction (PFC).
Minimal starting current.
Maximum power output between -40°C and +60°C.
DC-OK relay.
Current sharing function included.
Plug-in connectors for hot-swapping.
3-year warranty.

More information or a quote